How energy efficiency is improved
Powerful function modules in the ecos504/505 integrate the regulation of the room temperature, lighting and sunshading to create a comfortable room climate with minimum energy consumption
Part of the SAUTER modulo 5 system family
Modular room automation station (AS) for up to eight rooms or eight flexible room segments
BACnet/IP communication (EN ISO 16484-5) as BACnet Building Controller (B-BC)
The ecoUnit 3 and ecoUnit 1 room operating units enable individual adjustment of the room climate
Optimises energy consumption thanks to presence function, window contact monitoring, demand-controlled ventilation, control of lighting and window blinds, and time-dependent setpoint specification
Function libraries for climate, lighting and sunshading
Expansion bus for remote ecoLink modules, ecoUnit room operating units and EnOcean wireless interface
KNX interface to connect KNX operating units, sensors and actuators
Integrated KNX tunnelling function (KNX/IP) for the commissioning of KNX with ETS
DALI interface with DALI bus power supply for the connection of DALI electronic ballasts (EB) and DALI sensors
Web-based commissioning tool for DALI network
SMI interface (SMI/SMI LoVo) for activating SMI motors for sunshading (window blinds, roller shutters)
Integrated tunnelling function for commissioning with SMI-easyMonitor
RS-485 half duplex, electrically isolated interface for Modbus/RTU, Modbus/ASCII
Baud rate 600 to 115,200 bit/s with configurable RS-485 network resistors
Modbus master with up to four simultaneous communication profiles
Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools
Physical M-Bus interface and RS-232 interface for external M-Bus level converters
Supports M-Bus baud rates of 300 to 38,400 bit/s
M-Bus master function with up to four simultaneous communication profiles
Integrated tunnelling function for commissioning and monitoring with M-Bus tools
Time programme and calendar function; data recording
Integrated moduWeb web server (EY-RC504F101 only)
Integrated (EYRC504F202 only) or licensable MQTT functionality (MQTT Broker / Client)
Engineering/programming using SAUTER CASE Suite (based on IEC 61131-3)
Integration into the building management system via BACnet/IP with Ethernet interface
Devi caricare i contenuti da reCAPTCHA per inviare il modulo. Si prega di notare che in questo modo si condividono i dati con provider di terze parti.
Ulteriori informazioni